WIPIVERSE All articles

Voltage sag

Voltage sag, also frequently referred to as a voltage dip, is a short-duration reduction in the Root Mean Square (RMS) voltage magnitude. According to technical standards such as IEEE 1159, a voltage sag is typically defined as a decrease in voltage to between 10% and 90% of the nominal voltage at the power frequency, lasting for a duration of half a cycle to one minute.

Causes

Voltage sags are primarily caused by sudden increases in electrical load or faults within the power distribution system. Common triggers include:

  • Starting of heavy machinery: Large induction motors require high levels of current (inrush current) during startup, which can cause a momentary drop in voltage across the local network.
  • System faults: Short circuits or grounding faults on a parallel branch of the power grid often result in a sag until protective devices, such as circuit breakers or fuses, clear the fault.
  • Environmental factors: Lightning strikes or contact between power lines and external objects (e.g., tree branches) can create temporary faults leading to sags.

Characteristics

The severity of a voltage sag is determined by two main factors: magnitude and duration. The magnitude refers to the remaining voltage during the event, while the duration is the length of time the voltage remains below the specified threshold. Unlike a power outage or "blackout," the circuit remains energized during a sag, albeit at a lower potential.

Impact

Voltage sags are a significant concern in power quality management because they can disrupt the operation of sensitive electronic equipment. Impacts include:

  • Data loss: Uninterruptible power supplies (UPS) may fail to trigger fast enough, causing computers or servers to reboot.
  • Industrial disruption: Programmable logic controllers (PLCs) and variable speed drives may trip, leading to the shutdown of entire production lines.
  • Hardware damage: Repeated sags can cause thermal stress or mechanical wear on certain types of electrical components over time.

Mitigation

To minimize the effects of voltage sags, various power conditioning technologies are employed. These include constant voltage transformers (CVTs), superconducting magnetic energy storage (SMES), and the installation of UPS systems to provide bridge power during the duration of the sag.