Safety integrity level

Safety integrity level (SIL) is, in functional safety, a discrete classification of the reliability or risk-reduction performance required of a safety function implemented by electrical, electronic or programmable electronic (E/E/PE) systems. It is defined in the IEC 61508 series of standards as the relative level of risk reduction provided by a safety instrumented function (SIF) — i.e. a measure of the performance that the function must achieve. The concept is most closely associated with IEC 61508, the generic international standard for functional safety of E/E/PE safety-related systems, first published between 1998 and 2000, with a second edition issued in 2010. A further edition has been reported as in preparation.

The four levels

Under IEC 61508, four safety integrity levels are defined: SIL 4 is the highest (most dependable) and SIL 1 the lowest. Each level corresponds to a numerical band of target failure measures, and the applicable measure depends on the mode of operation of the safety function:

  • In low demand mode, the target is the average probability of a dangerous failure on demand (PFD_avg).
  • In high demand or continuous mode, the target is the average frequency of a dangerous failure per hour (PFH).

The bands given in IEC 61508-1 (Tables 2 and 3) are, in outline:

SIL Low demand: PFD_avg High demand/continuous: PFH (per hour)
4 ≥ 10⁻⁵ to < 10⁻⁴ ≥ 10⁻⁹ to < 10⁻⁸
3 ≥ 10⁻⁴ to < 10⁻³ ≥ 10⁻⁸ to < 10⁻⁷
2 ≥ 10⁻³ to < 10⁻² ≥ 10⁻⁷ to < 10⁻⁶
1 ≥ 10⁻² to < 10⁻¹ ≥ 10⁻⁶ to < 10⁻⁵

These bands are also commonly expressed as risk reduction factors (RRF), i.e. the reciprocal of the PFD or PFH band. IEC 61508 also sets a lower limit on the target failure measure claimable for a single E/E/PE safety-related system — 10⁻⁵ on demand in low demand mode, and 10⁻⁹ per hour in high demand or continuous mode — reflecting what relatively complex systems are considered able to achieve.

Two components of a SIL claim

IEC 61508 groups SIL requirements into two broad categories, and a device or system must satisfy both to support a claim at a given level:

  • Hardware safety integrity, addressed through probabilistic analysis of random hardware failures, together with architectural constraints expressed through hardware fault tolerance (HFT) and safe failure fraction (SFF), and through the routing options (Route 1H and Route 2H) introduced in the 2010 edition.
  • Systematic safety integrity, addressed through requirements for avoiding and controlling systematic faults, and expressed in the 2010 edition through systematic capability (SC 1 to SC 4), which rates the confidence that an element meets the systematic integrity requirements of a given SIL — for example through a rigorous development process, proven-in-use evidence, or compliant pre-existing software.

Determination of SIL

The SIL of a safety function is determined by risk analysis: the unmitigated risk of a hazard is compared with a tolerable risk target, and the required risk reduction is correlated with a SIL. IEC 61508 Part 1 states that the standard does not itself specify the SIL required for any particular safety function, nor mandate a method; it provides a risk-based framework, and IEC 61508-5 gives informative examples of quantitative and qualitative methods. These include a quantitative method, risk graphs, layer of protection analysis (LOPA), and hazardous event severity and risk matrices. Sector standards specify the SIL values applicable in their fields.

Related and sector standards

SIL is used, with varying definitions and limits, in standards derived from or related to IEC 61508, including IEC 61511 (process industry), IEC 61513 (nuclear industry) and IEC 62061 (machinery safety, limited to SIL 1–3). Other frameworks use analogous but distinct scales rather than SIL: ISO 26262 for road vehicles uses Automotive Safety Integrity Levels (ASIL A–D); ISO 13849-1 for machinery uses Performance Levels (PL a–e) and follows a separate tradition rather than deriving from IEC 61508. Railway software integrity levels appear in standards such as EN 50716.

Certification and criticism

Independent certification bodies (for example, under the CASS scheme, or organisations such as TÜV, UL or CSA) assess whether devices or development processes meet a particular SIL. IEC itself states that it does not provide attestation of conformity, so a "SIL certificate" is a statement by a certification body under its own scheme. Commentators have noted a number of difficulties with the concept, including inconsistent definitions across standards bodies, the treatment of SIL as a property of a component rather than of a safety function, and the difficulty of estimating systematic integrity, particularly for software. A commonly emphasised point is that an element described as "SIL 3 capable" does not by itself make a safety function compliant at SIL 3: the complete function — sensors, logic and final elements — must meet the target, the architectural constraints and the systematic capability, under the conditions stated in the element's safety manual.